MAG816 - Installation and Operation Manual 19
5.2 Double Action Mode
The purpose of introducing a DOUBLE Action mode is to avoid false alarms. Where
MAG816 has been programmed to function in this mode, in the case of a re signal,
the panel does not alarm at once but waits for the alarm event to be repeated within a
specic time interval - Figure 25. The time interval has been set by default and cannot
be adjusted. For MAG816 it is 3 minutes.
In order to program the re alarm panel for Double Action mode:
Set a jumper on the DOUBLE terminal of the main module - Figure 10.
• Press
to introduce changes.
Figure 25.
EXAMPLE 1: In this case the re panel will not activate the sounders and the signalization
on the front panel because during time interval 2 no second alarm signal is generated.
EXAMPLE 2: In this case the re panel will activate the sounders and the signalization
on the front panel because during time interval 2, two alarm signals are generated.
5.3 Instant Action Mode
Where in the armed site there are zones, which need the sounders and the light
indicators to be enabled instantaneously, the panel provides instant action working
mode. This mode can be programmed individually for every single zone, depending on
its designation. In instant action mode, in case of an alarm event occurring in the zone,
the sounders are immediately enabled, i.e. this mode is of priority by zones compared to
Double Action and Sounder Delay modes.
In DOUBLE action mode of operation, where there is NO jumper on instant action
terminals of the zone expander, ONLY detectors can be connected to each zone circuit,
and if a jumper has been set - that allows connecting both detectors and call points.
In order to program Instant Action mode for a selected zone:
Set a jumper on the terminal that corresponds to the number of the zone - Figure 13.
• Press
to introduce changes.
Example: If there are call points connected in ZONE 1, for the system to function properly
there must be a jumper at its zone expander at z1 position.