MAG2P - 2 Zone Fire Panel
2 programmable zones
Active end of line monitoring and head removal
30 fire detectors per zone
Unlimited number of call points per zone
Integral evacuate alarm button
‘Class change’ facility
Enable/disable security key
One man walk test facility
Volt free fire change over relay
Volt free fault change over relay
Individual sounder circuit fault ID
Individual zone/sounder isolate
Cer
tified to
EN54–2/4
Requires only 1x12v battery
MAG2P - ABS casing
Made in
EU
EN54
MAG2
2 Zone Fire Panel
Metal Casing
OUTPUTS Sounder 1 24V (max 300mA fused)
Sounder 2 24V (max 300mA fused)
Fault/fire relay Volt free 500mA @ 24V (max load)
Auxiliary output 24VDC (300mA fused)
ENVIRONMENT Working Temperature 0 to 40ºC
Storage Temperature -20 to 60ºC
Humidity 0 - 95%
Dimensions MAG2P 340 x 290 x 100mm
Dimensions MAG2 200 x 290 x 80mm
Weight MAG2P - 2.1Kg MAG2 - 2.7Kg
INPUTS Max detectors per zone 30
Thresholds for 0 - 2 mA (Fault condition)
zone conditions 2 - 6 mA (Normal condition)
6 - 110 mA (Fire condition)
110 mA - Short (Fault condition)
POWER Mains fail consumption 50mA
Mains supply 230 VAC ± 10%
Standby supply 1 x 7ah 12V S.L.A. Battery
Power availability 0.7 amps
MAGPro Fireline Catalogue.qxp_Layout 1 16/06/2014 15:35 Page 13